LG Cementitious Fire Retardant Coating for Structural Steel

Steel structure is non-combustible , but it will lose strenghth within 20 minutes in a fire condition. LG can be promoted the fire resistance of steel structures up to 3 hours.

¢ñ .Technical
Specifications (tested to GB14907-2002 ¡°Fire Resistive Coating for Structural Steel)

Appearance: viscous liquid

Touch Dry : 3 hous

Adhesion Strength: 0.30MPa

Compressive Strenghth: 2.5MPa

Dry Density: 550kg/m3

Water Resistance:24 hours

Freeze-thaw Resistance: Done 15 times without any defets

Fire Resistance: It can provide up to 180 minutes fire resistance for 24 mm dry film thickness(dft)

¢ò . Application

•  First clean away the dust, grease and other contaminants on the substrate before application and apply anti-rust paint.

•  The mixing ratio of water: KT interfacial agent: LG coating should be (120~140):2:100 for first mixing. For the sequent mixing, the ratio of water: KT interfacial age:LG should be (120~140):2:100. Add some Kt interfacial agent to the water and stir thoroughly , then add LG. Use immediately within 30 minutes after mixing.

•  It should be applied by spray for 5 mm for first application. It can be applied by spray or butsh for the sequent application for 8~10mm dft until achieve required thickness. Allow 24 hours drying between application. It can provide up to 3 hours fire resistance depending on the dry film thickness(dft):

Fire resistant rating/h

15

2

2.5

3

Dry film thickness(dft) / mm

11

15

19

23

•  Finishing: The coating layer is particle-like if it is applied by spray. If smoothness is required, it should be done at the last coat. The coating can be coated on decorative paint if required.

¢ó . Storage and transportation

It is available in 50kg barided sacks. It should be stored in a dry area for half year. Avoid rainfall when stored and transported.

For further information, please contact us:

Tel: +86-13568979897

Email: horsecar@163.com hskuan@hotmail.com